The HTACC-LT-606Z Displacement Sensor is the “eye” monitoring rotor axial shift and shaft vibration. It changes tiny rotor movements into electric signals, which go to the monitoring system, triggering an alarm if values spike. Often, the sensor itself is fine. The issue is sloppy electrical wiring or poor shielding during install, which “twists” the signal. This leads to jumpy readings and false trips, or worse, missed warnings about real danger.
Mechanical fastening is basic, but the real key to whether this “eye” sees clearly is correct electrical wiring and solid signal shielding. Here is how to do every step right, from detailed wiring standards to the strict requirements for shielding.

I. Electrical Wiring Standards: Every Step for Signal “Fidelity”
Wiring the LVDT displacement sensor HTACC-LT-606Z is all about making sure the signal moves completely and without loss from the sensor to the monitor. Cable, terminals, polarity, insulation, any part will “corrupt” the signal.
1. Cable Selection: Use the Right Wire, Stop Interference
For the HTACC-LT-606Z signal line, you should always choose specialized cable with double shielding. The outer layer is metal braid, the inner is aluminum foil. This dual barrier blocks most high-frequency electromagnetic noise. You must not use standard single-core or unshielded wire. The signal will be “eaten up” by the magnetic fields from plant motors and drives during transit. By the time it hits the monitor, it’s distorted. A real displacement of 0.1mm might show up as 0.3mm, or even jump randomly.
Wire gauge matters, too. For the 2-core signal line, use stranded copper wire, 0.5 to 0.75mm². Stranded wire handles vibration better than solid wire; the constant shaking of the turbine won’t break the conductors. Too thin, the signal degrades too much. Too thick, the terminal won’t accept it, and routing is harder.
If you lack the specialized cable, and need a temporary fix, contact us to check for compatible types. Do not simply grab random stock cable; it makes later signal debugging a nightmare.
2. Terminal Connection: Crimp it Tight, Keep the Signal Solid
The connection between the wire and the sensor/monitor terminals must not be loose. The HTACC-LT-606Z displacement sensor uses small crimp terminals. After stripping the wire, you must attach a cold-pressed terminal pin first, then insert it into the sensor connection hole and tighten the screw.
Strip length must be spot-on, usually 1–2mm longer than the terminal pin’s depth. Strip too long, and bare copper sticks out, risking short circuits with nearby terminals. Strip too short, the wire doesn’t fully enter the terminal, the crimp grips the insulation, and vibration will quickly pull it loose. Use a dedicated crimping tool, squeezing until the jaws auto-release, ensuring a firm bite between copper and terminal. Pull the wire—if it doesn’t move, it’s good.
Some technicians cut corners and just twist the bare copper around the terminal screw. This is strictly forbidden. Constant turbine vibration will loosen the screw, causing intermittent signal loss. By the time you notice, the rotor might have already grazed the casing slightly.
3. Polarity Check: Get it Wrong, the “Eye” is Blind
The HTACC-LT-606Z is a DC-powered sensor with defined power and signal polarities. Reversed connection stops the sensor from working or, worse, fries the internal circuits.
Sensor terminals are typically marked “V+”, “V-”, “S+”, “S-”. “V+” goes to 24V DC positive, “V-” to negative. “S+” and “S-” connect to the monitor’s positive and negative signal inputs. Always check the power polarity with a multimeter before wiring, then match wire for wire to the sensor manual’s pin-out. Don’t guess by color. Different manufacturers use different color codes; red isn’t always positive.
Reversed polarity is simple: either the sensor outputs nothing (monitor shows “No Data”), or the signal output is inverted (monitor shows negative displacement, the opposite of reality). If you see this after wiring, kill the power and check polarity first. Don’t blindly assume the sensor is faulty. Contact us for the pin-out diagram to verify connections quickly.
4. Insulation: Keep Oil and Steam Out, Signal In
Near the turbine bearing housing, oil, moisture, and steam are everywhere. The insulation on terminals and wire joints must be watertight.
After wiring, each terminal must be wrapped individually with insulating tape, at least three layers thick, covering the entire terminal and the bare wire joint. The tape edge should extend 2–3mm beyond the insulation jacket. Don’t wrap all terminals together in one lump; if one terminal’s insulation fails, it shorts all connections to ground.
For the wiring hole passing through the bearing housing wall, seal the gap with putty. Choose an oil- and high-temperature-resistant putty that cures into an elastic seal. This blocks oil from entering the sensor body and prevents moisture from aging the wire insulation.
II. Signal Shielding Rules: Block the Noise, Get a “Clean” Signal
Power plants are electromagnetically noisy. Magnetic fields from motors, drives, and high-voltage cables will all target the sensor’s tiny signal. Shielding the HTACC-LT-606Z is like “building a wall” for the signal, keeping interference out.

1. Shield Grounding: Single-Point Ground is Law
The cable’s double shielding must be grounded at only one end. No exceptions. Either connect it to the dedicated grounding point at the sensor side or the grounding bar in the monitoring cabinet. Never ground both ends.
Grounding both ends creates a “ground loop.” The ground potential might differ between the sensor and cabinet, causing current to flow in the shield, which creates new interference signals—worse than no shielding at all. Ground resistance must be below 4Ω, measured with a ground resistance meter. If it fails, clean the grounding bar (remove oxidation) or install a separate grounding rod.
Use dedicated yellow-green grounding wire, 1.5mm² or thicker. Crimp one end to the ground terminal, and firmly secure the other end to the grounding bar. Poorly grounded shielding—using thin wire or just twisting it on—is useless.
2. Routing Isolation: “Clear the Way” from High Power
Sensor cables must be routed away from high-power lines. Maintain at least 1 meter separation from 380V and up power cables, and high-voltage excitation cables. Separation from variable frequency drive (VFD) output cables should be over 1.5 meters.
When crossing, the cables must cross at a 90-degree angle, never run parallel. Even 20 centimeters of parallel running allows the strong magnetic field to induce noise in the sensor cable, making displacement readings jump. For example, if the sensor cable runs parallel to the feedwater pump motor’s power line, the displacement reading will spike suddenly when the motor starts and drop back when it stops. Classic routing interference.
Cables must be secured in dedicated plastic or metal trays, and the trays must be grounded. Do not bundle them directly to steam pipes or metal supports. Heat and vibration age the cables faster, and metal supports can act as interference “conduits.”
3. Shield Integrity: No “Gaps” in the Defense
The protection offered by the shielding depends on its continuity. Any break or damage is an “entry point” for interference.
Avoid squeezing or dragging the cable during routing. If the metal braid is worn or snapped, the damaged spot loses all shielding. When passing through metal holes, use rubber grommets to stop sharp edges from cutting the shielding layer.
Shielding treatment at cable joints is also vital. Do not strip the shield too short. Leave a 3–5mm overlap, fix it with a shield clamp to the sensor’s ground point, or secure it with copper wire before grounding. Never leave the shield floating. A floating shield acts like an “antenna,” actively receiving surrounding electromagnetic interference.
4. Interference Source Avoidance: Stay Away from “Hot Zones”
The installation location for the HTACC-LT-606Z should inherently avoid high-interference equipment. Do not install it near VFD cabinets, high-voltage disconnect switches, or large motor junction boxes. These devices generate strong magnetic fields during operation that even double shielding struggles to fully block.
If the sensor must be installed in a high-interference zone, beyond double-shielded cable, you need to add magnetic ferrites to the signal lines. Place the ferrites at both ends of the cable, near the sensor and the monitor, to absorb high-frequency noise. Choose nickel-zinc material ferrites that match the cable diameter, and secure them with zip ties to prevent vibration-induced movement.
III. Final Checks: The Last Barrier Before Power-Up
After wiring and shielding, do not power up immediately. Perform two checks for total safety.
First is a continuity test. Use a multimeter’s continuity function to check the path from sensor “V+” to power positive, and “V-” to power negative. Then, check the insulation resistance between “V+” and “V-”, and between “S+” and the casing. Resistance must be above 10MΩ to pass, preventing short circuits or grounding issues.
Second is a simulated signal test. Apply 24V power to the sensor, then move a metal target close to the probe tip and watch the monitor reading. If the reading changes smoothly without jumping, your wiring and shielding are good. If the reading jumps wildly or is non-responsive, recheck the shield grounding, terminal connections, and polarity.
End Note: Signal Stability is in the “Details” of Wiring and Shielding
For the HTACC-LT-606Z displacement sensor, there’s no such thing as “good enough” for electrical wiring and shielding. The crimp on every terminal, the ground on every shield segment—they directly control the accuracy of rotor displacement monitoring. Many displacement sensor “failures” in power plants turn out to be small issues: loose connections, broken shields, or reversed polarity.
If you are installing the HTACC-LT-606Z and encounter no signal, interference despite shielding, or are unsure if your routing meets standards, do not proceed blindly. Contact us. Our engineers can help you debug the issue step-by-step. We also provide compatible, specialized shielded cables and wiring kits, ensuring your sensor installation is done right the first time, providing stable and reliable data to secure the turbine rotor.
Post time: Nov-19-2025
