The 4000TDK-15-01 LVDT sensor talks directly to the turbine’s steam flow. It’s critical. The iron core links hard to the main steam valve stem; the stem moves, the core moves, and the electricity it makes is the control system’s only guide. This area? Always hot—200°C to 300°C. Pipe heat, steam leaks, it all hits the sensor.
A seized core is a massive problem. Heat warps the core and sleeve, the gap disappears, maybe less than 0.01mm. Add burnt oil, rust, it locks up. Signal freezes. The control system is blind, it pushes too hard—valve opens too wide, turbine speeds out of control. Or closes too much, load drops suddenly. Stop seizing. It starts with installation—the first bolt—and continues with every daily check.

I. Installation Rules: Don’t Cause the Problem Yourself
Seizing begins with heat warpage and being out of line. Before putting it in, check the core—no scratches. The 4000TDK-15-01 LVDT sensor alloy is tough, but a ding makes a burr. Heat makes the burr swell. It scratches the sleeve wall. Starts as stiff movement, ends up locked. Slide your finger down the core: smooth, no bumps. If bad, replace. Never try to fix it with sanding—you change the diameter, you wreck accuracy.
But often the sensor is fine. Bad installation ruins everything. Concentricity, how you bolt it down, how you shield the heat—it all matters.
Alignment Check: No “Running Sideways” for the Core
- If the core and stem are off by more than 0.1mm, the core “grinds unevenly” in the sleeve. Hot metal is soft. That grinding kills the gap on one side—seizing. The other side has too much gap—signal drift.
- Calibrate with a dial gauge: Mount the gauge to the sensor bracket. Touch the probe to the core end. Move the valve stem full travel by hand. The dial shouldn’t jump more than 0.05mm.
- If it’s too much, move the sensor bracket. Add a thin shim if needed to make it flat. Keep adjusting until it’s straight. One plant skipped this. Sensor seized in 3 days. They fixed the alignment; it’s run fine since.
- Need help aligning or don’t have the tools? Contact us. We can send tech support. Stop wasting time ripping it apart again and again.
Mounting & Heat Break: Keep the Oven Off the Sensor
- Don’t bolt the sensor right onto the valve. High pipe heat travels straight through the metal bracket to the sensor body. Inside, it’s 50°C hotter than the room.
- Use a bracket with heat shielding. Put a 5mm-thick mica pad between the bracket and the valve to break the heat.
- Use high-temp thread-locker on the bolts. Turbine vibration shakes screws loose, and the sensor shifts, losing alignment. The thread-locker holds the bolts fast, even at 300°C.
- Tighten to the right torque. Not too tight (you’ll crack the housing), not too loose (it’ll shake free).
Cable Routing: Interference Can “Look Like” Seizing
- The cable doesn’t seize the core, but electrical noise messes up the signal. The bad signal looks like a seizing fault. The 4000TDK-15-01 signal cable must be double-shielded.
- Ground the outer braid at only one end—at the monitoring cabinet ground bar. Never share a ground with power cables.
- Route it far from high-voltage cables and VFDs. Keep it over 1 meter away from 380V+ power lines. If they cross, make a 90-degree angle to cut magnetic noise.
- Anchor the cable firmly. Stop vibration from loosening the connectors and making the signal unstable.

II. Usage & Upkeep: Daily Habits Prevent Big Problems
Installation is only the start. Maintenance steps keep the seizing away longer and kill risks early.
Routine Checks: Simple Touch for Early Warning
- 1. Watch the Signal: Look at the DCS display. When the valve moves, the signal must be smooth, no jumps, no freezing.
- 2. Check the Heat: Use a thermal gun on the sensor body. Over 300°C? Your heat shield failed. Check the mica pad or add cooling fins.
- 3. Wipe it Down: Use compressed air to clean dust and oil off the sensor. Stop that mess from getting into the sleeve.
- Disassembly Check: Pull the core during a shutdown. Look for scratches, rust. Check the inner ceramic coating—is it good? Light scratches? Gently use 600-grit paper with some grease. Deep scratches or flaking coating? Replace the sensor now. Don’t push your luck.
Environmental Control: Reducing High-Temperature Shock
- Steam leaks from the main valve are why the sensor gets so hot. Find leaks, stop them fast. Keep hot steam off the sensor.
- You can put a stainless steel cover over the sensor. Leave a 5mm air gap for insulation. Drill holes in the cover for air to move.
- Rain or high humidity? Keep water out. Wrap the cable connector with waterproof tape. Tighten the tail cap on the sensor end. Water plus heat equals corrosion, which leads to seizing.

III. Anomaly Handling: Fast Moves for Initial Seizing
Signal is a bit jumpy? Could be early seizing. Don’t trip the unit yet. Try moving the valve stem a few times manually. Use that mechanical force to free the core. Check the signal. If it’s back to normal, it was temporary—just dirt or oil. Clean it next shutdown. If the signal is still bad, you must stop, take it apart, and swap out the damaged bits.
When replacing, use only the 4000TDK-15-01 LVDT sensor. No substitutes. Different cores have different clearances and materials. Mixing them will seize. New sensor? You must re-calibrat alignment and signal output. Make sure it talks right to the control system.
Conclusion: Cool Core, Safe Unit
Stopping the 4000TDK-15-01 from seizing is never one magic fix. Right material is the base. Good installation is the guarantee. Daily maintenance is the long game. Everything aims at “less heat warp, less drag.” That’s how the core stays slick in the heat, and your signal stays true.
Did your LVDT sensor seize from heat? Are you installing a new unit and need to check the parts? Contact us. We can supply the OEM 4000TDK-15-01 spares. We track it from selection to upkeep. Get your main steam valve control stable and keep your unit running safe.