In thermal power plants, controlling the water quality of the generator stator cooling water system is crucial. The 2402B conductivity meter, a core device for monitoring cooling water purity, directly reflects the ion concentration in the water. However, when operators observe a decrease in the 2402B conductivity meter reading after hydrogen replenishment, does this necessarily mean that the water quality has truly improved? This question requires a comprehensive analysis of the conductivity meter’s operating principle, the chemical effects of hydrogen replenishment, and the operational logic of the cooling water system.
I. The Core Function of the 2402B Conductivity Meter
The 2402B conductivity meter is an instrument based on electrochemical measurement principles, used to monitor the total ion concentration in cooling water in real time. It operates by applying a constant voltage between two parallel electrodes and measuring the current to calculate the solution’s conductivity. Conductivity is directly proportional to the concentration of conductive substances such as dissolved inorganic salts and metal ions in the water. Therefore, a lower 2402B conductivity meter reading generally indicates a lower ion content and higher water purity.
In generator stator cooling water systems, the set thresholds for the 2402B conductivity meter are typically very strict. For example, high-quality cooling water should have a conductivity below 1 μS/cm. Exceeding this range can cause problems such as copper coil corrosion and insulation degradation. Therefore, operators closely monitor changes in the conductivity meter readings and maintain stable water quality through water replenishment, ion exchange, or chemical treatment.
II. Chemical Effects of Hydrogen Replenishment and Conductivity Changes
Hydrogen replenishment is a routine operation in thermal power plant generators. Generators must maintain internal hydrogen purity to improve cooling efficiency and reduce energy consumption. Replenishment typically involves injecting high-purity hydrogen into the generator system while discharging some of the gas to maintain pressure balance. This process can indirectly affect the conductivity of the cooling water system.
When hydrogen is injected into the system, some of it dissolves in the cooling water, forming tiny bubbles. Hydrogen itself is an inert gas and does not directly participate in ionic reactions, but its dissolution may dilute the ion concentration in the cooling water. For example, if the cooling water already contains impurities such as Na⁺ and Cl⁻, the addition of hydrogen will reduce the ion density per unit volume, resulting in a decrease in the 2402B conductivity meter reading. This phenomenon does not represent a true improvement in water quality, but rather the result of physical dilution.
Furthermore, hydrogen refilling may be accompanied by changes in cooling water temperature. Hydrogen injection increases system heat, causing the cooling water temperature to rise. According to the temperature compensation formula for conductivity, increased temperature reduces the viscosity of the solution and accelerates ion migration, artificially lowering the conductivity meter reading. For example, after hydrogen refilling, a power plant recorded a decrease in the 2402B conductivity meter reading from 1.2 μS/cm to 0.9 μS/cm. However, laboratory retesting revealed no significant change in the ion concentration in the cooling water, indicating that temperature effects were a primary factor in the decrease.
III. Decreased conductivity does not necessarily mean improved water quality: A comprehensive assessment is required
While a decrease in the 2402B conductivity meter reading may indicate improved water quality, this conclusion must be verified in conjunction with other parameters. For example, if conductivity decreases while the pH, total hardness, or copper ion concentration of the cooling water also decreases, it can be preliminarily judged that water quality has indeed improved. However, if only conductivity decreases while other indicators remain unchanged or even exhibit abnormal fluctuations, alert to potential risks.
The following scenarios require specific investigation:
- Short-term effects of hydrogen dissolution: After hydrogen replenishment, hydrogen may temporarily create localized areas of low ion concentration in the cooling water, causing abnormal fluctuations in the readings of the 2402B conductivity meter. For example, in one case, operators observed a sudden drop in conductivity after hydrogen replenishment, but the reading returned to its original value several hours later, indicating that the physical dilution effect of hydrogen is a short-term phenomenon.
- Ion exchange system anomalies: If the cooling water system relies on ion exchange resin to remove impurities, hydrogen replenishment may interfere with the resin’s regeneration cycle. For example, if the resin becomes saturated and cannot effectively absorb ions, the conductivity meter’s 2402B reading may decrease, even though the water quality has actually deteriorated.
- Conductivity meter malfunction: Aging or contamination of the 2402B’s electrodes may also cause distorted readings. For example, scaling on the electrode surface can reduce the current response, causing conductivity readings to be artificially low.
IV. How to Scientifically Assess Water Quality Changes?
To accurately determine whether water quality has truly improved after hydrogen refilling, operators should take the following measures:
- Multi-parameter Monitoring: In addition to the 2402B conductivity meter, monitor indicators such as pH, dissolved oxygen, total hardness, and copper ion concentration. For example, if conductivity decreases but copper ion concentration increases, this may indicate a risk of localized corrosion in the cooling water system.
- Laboratory Retesting: Regularly sample the water and send it to the laboratory for ion concentration testing using standard methods to avoid temperature compensation errors in the conductivity meter.
- Historical Data Comparison: Compare current conductivity data with historical trend charts to determine whether changes are within normal fluctuations. For example, if the 2402B conductivity meter reading has been stable at 0.8-1.0 μS/cm for a long time and drops to 0.6 μS/cm after hydrogen refilling without any other abnormalities, the water quality can be considered improved.
The 2402B conductivity meter is an essential monitoring tool for generator stator cooling water systems. Its readings quickly reflect dynamic trends in water quality. However, a decrease in conductivity after hydrogen replenishment does not necessarily indicate improved water quality; it could be the result of hydrogen dilution, temperature effects, or equipment malfunction. Operators must comprehensively assess water quality through multi-parameter linkage, laboratory retesting, and historical data analysis to avoid misjudgment that could lead to equipment damage or safety incidents.
When looking for high-quality, reliable oil filters, YOYIK is undoubtedly a choice worth considering. The company specializes in providing a variety of power equipment including steam turbine accessories, and has won wide acclaim for its high-quality products and services. For more information or inquiries, please contact the customer service below:
E-mail: sales@yoyik.com
Tel: +86-838-2226655
Whatsapp: +86-13618105229
Yoyik offers various types of power plants spare parts for steam turbines, generators, boilers as below:
pneumatic pressure regulator AW30-02-D
Level switch YKJD220-BH-465-365-135
types of pressure measurement BPSN4KB25XFSP12
Pressure switch 880300
LVDT Sensor 2000TD-E
Water pressure pulsation monitor with pressure transmitter SYM-1
thermometer price WSS-581W
Vibration monitoring instrument CZJ-4D
High Speed Bus Power Transfer System MFC2000-3A
chneider AAPC SMART UPS SRT3000XLI
Differential pressure switch DK-0.15
led speed display MSC-2B
Cover vibration sensor PR9268/200-000
Analog Output Module HAO805
AC MCB DZ47-60-C60/3P
Torque Control Module SY-JB (Ver 2.10)
THERMOCOUPLE DESUPERHEATER WRNK-630B
Current Transducer FPA-A2-F1-PD2-011
ENETWORK COMMUNICATE ION MODULE 1756-EN2 TR
LVDT Sensor TD-1-0150-10-01-01
NEPM meter KV
Turning gear and flyweight proximity switch LJ12A3-4(2)Z/BY
Annunciator CJX-14
Double-layer corrugated tube GJC-BWGsh
GEAR SHAFT GT2111007
Pressure switch H100-612
tachometer shaft SCZ-04B
k thermometer TE-104
Cable AWM 2651 SB H604577
THERMOCOUPLE WRNR2-15
SWITCH PROXIMITY XS118BLFAL2
Oil temperature sensor YT315D M16 * 1.5
Transmitter S3(T)-VD-125A4B
Temperature probe WZPM2-201
Post time: Aug-12-2025